Application
Utilisé pour le raccordement final des habitations. Convient également à la distribution secondaire, notamment dans les immeubles de grande hauteur et les systèmes d’éclairage public.
Concentric and Split Concentric Cables used by distribution network operators when providing the final connection to domestic properties. Also suitable for sub main distribution and particularly used within high-rise buildings and street lighting systems.
Utilisé pour le raccordement final des habitations. Convient également à la distribution secondaire, notamment dans les immeubles de grande hauteur et les systèmes d’éclairage public.
BS 7870
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km | MAXIMUM DC RESISTANCE OF CONCENTRIC CONDUCTOR AT 20°C ohms/km | CURRENT CARRYING CAPACITY Amps | ||
| In Air | Clipped Direct | Enclosed in Conduit on a Wall | ||||||
| 1 | 25 | 13 | 300 | 1.2 | 1.3 | 127 | 119 | 105 |
| 1 | 35 | 14 | 390 | 0.868 | 0.91 | 158 | 147 | 128 |
| 3 | 25 | 23 | 650 | 1.2 | 1.3 | 97 | 90 | 84 |
| 3 | 35 | 25 | 820 | 0.868 | 0.91 | 120 | 112 | 103 |
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | MAXIMUM DC RESISTANCE OF AT 20°C ohms/km | CURRENT CARRYING CAPACITY Amps | ||||
| CONDUCTOR | Neutral | Earth | In Air | Clipped Direct | Enclosed in Conduit on a Wall | ||||
| 1 | 25 | 15 | 490 | 1.2 | 1.2 | 1.2 | 127 | 119 | 105 |
| 1 | 35 | 16 | 610 | 0.868 | 0.76 | 1.2 | 158 | 147 | 128 |
| 3 | 25 | 23.5 | 830 | 1.2 | 1.2 | 1.2 | 97 | 90 | 84 |
| 3 | 35 | 26 | 1030 | 0.868 | 0.76 | 1.2 | 120 | 112 | 103 |
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km | MAXIMUM DC RESISTANCE OF CONCENTRIC CONDUCTOR AT 20°C ohms/km | CURRENT CARRYING CAPACITY Amps | ||
| In Air | Clipped Direct | Enclosed in Conduit on a Wall | ||||||
| 1 | 4 | 8.5 | 140 | 4.61 | 4.8 | 42 | 41 | 37 |
| 1 | 16 | 12 | 370 | 1.15 | 1.2 | 100 | 99 | 88 |
| 1 | 25 | 14 | 550 | 0.727 | 0.76 | 135 | 130 | 117 |
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km | CURRENT CARRYING CAPACITY Amps | |||
| Metal-Coated Wires | Plain Wires | In Air | Clipped Direct | Enclosed in Conduit on a Wall | ||||
| 1 | 4 | 10 | 190 | 4.8 | 4.8 | 42 | 41 | 37 |
| 1 | 16 | 14 | 530 | 1.2 | 1.2 | 100 | 99 | 88 |
| 1 | 25 | 16 | 710 | 1.2 | 0.76 | 135 | 130 | 117 |
| 3 | 35 | 28.5 | 1900 | 0.76 | 0.55 | 129 | 120 | 110 |
Scroll horizontally to review complete specification columns.
Request Full TDSConcentric and Split Concentric Cables used by distribution network operators when providing the final connection to domestic properties. Also suitable for sub main distribution and particularly used within high-rise buildings and street lighting systems.