Technical Grade

TAAAC CONDUCTEUR

TAAAC Conductor Urban network capacity transformation, substation, power plant construction and general lines

CategoryHigh Temperature Conductor
SourceDTC Cable

Product Images

Product Overview

Application

Urban network capacity transformation, substation, power plant construction and general lines

Standards:

IEC 61089 / BS EN 50182

Technical Parameters

Specification Table 1

Cross Sectional areaNa/Dia of wireApproximatelyDC conduvtor Resistance at 20℃,maxCalcuated breaking load minCurrent Carrying capacityStandard Delivery lenght
Overall diameterNet weight
mm²Pcs/mmmmKg/kmΩ/kmkgfnAm
15019/3.20164190.19102270222687005000
20019/3.7018.55600.14303030297248505000
24019/4.00206550.12203490342369453000
MORE
30037/3.2022.48210.095844304345810903000
40037/3.7025.910970.073758905778013252000
51037/4.2029.414140.057174607318215652000
66061/3.7033.318120.044897209535318401500
85061/4.2037.823350.03471230012066321751000
98091/3.7040.727160.03021450014224523801000
103091/3.8041.828650.02861532015028924651000
126091/4.2046.235010.0234183501800132800500

Specification Table 2

Nominal Cross section areaStructure [number x diameter of wire]Calculation area cross cestionApprox. Diameter of conductorMin.breaking strengthDC Resistance of conductor at 20℃Approx Mass of conductorCurrent Carrying capacity
mm²nmmmm²mmkNΩ/kmKg/kmA
120192.80117.014.0017.50.2493320.1566
150193.15148.115.7522.20.1970405.1659
200193.65198.818.2529.20.1467543.9798
MORE
240194.00238.820.0034.20.1220654.5897
300373.20297.622.4044.50.0986816.01036
400373.70397.825.9058.00.07371097.01258
510374.20512.629.4073.30.05711413.01491
660613.70655.933.3095.60.04481812.01753
850614.20845.137.80120.90.03422334.02073
980613.70978.440.70142.70.03022714.02272
1030913.801032.141.80150.50.02862864.02353
1260914.201260.846.20180.30.02343499.02672
16001274.001595.952.00228.50.01864440.03083
20201274.502019.558.50289.00.01475616.03540
25001275.002493.765.00357.00.01186937.03988

Scroll horizontally to review complete specification columns.

Request Full TDS

Structure & Technical Illustration

TAAAC CONDUCTEUR

TAAAC Conductor Urban network capacity transformation, substation, power plant construction and general lines

Product image and technical reference.

Related Products

TACSR TACSR/AW CONDUCTEUR

TACSR TACSR/AW CONDUCTEUR

View Details
ACSS ACSS/TW CONDUCTEUR

ACSS ACSS/TW CONDUCTEUR

View Details
STACIR STACIR/TW CONDUCTEUR

STACIR STACIR/TW CONDUCTEUR

View Details
AUTRE HTLS CONDUCTEUR

AUTRE HTLS CONDUCTEUR

View Details
TAAAC CONDUCTOR | DTC Cable