Application:
Urban network capacity transformation, substation, power plant construction and general lines

TAAAC Conductor Urban network capacity transformation, substation, power plant construction and general lines LEAVE MESSAGE SEND E-MAIL
Urban network capacity transformation, substation, power plant construction and general lines
IEC 61089 / BS EN 50182
| Cross Sectional area | Na/Dia of wire | Approximately | DC conduvtor Resistance at 20℃,max | Calcuated breaking load min | Current Carrying capacity | Standard Delivery lenght | ||
| Overall diameter | Net weight | |||||||
| mm² | Pcs/mm | mm | Kg/km | Ω/km | kgf | n | A | m |
| 150 | 19/3.20 | 16 | 419 | 0.1910 | 2270 | 22268 | 700 | 5000 |
| 200 | 19/3.70 | 18.5 | 560 | 0.1430 | 3030 | 29724 | 850 | 5000 |
| 240 | 19/4.00 | 20 | 655 | 0.1220 | 3490 | 34236 | 945 | 3000 |
| 300 | 37/3.20 | 22.4 | 821 | 0.0958 | 4430 | 43458 | 1090 | 3000 |
| 400 | 37/3.70 | 25.9 | 1097 | 0.0737 | 5890 | 57780 | 1325 | 2000 |
| 510 | 37/4.20 | 29.4 | 1414 | 0.0571 | 7460 | 73182 | 1565 | 2000 |
| 660 | 61/3.70 | 33.3 | 1812 | 0.0448 | 9720 | 95353 | 1840 | 1500 |
| 850 | 61/4.20 | 37.8 | 2335 | 0.0347 | 12300 | 120663 | 2175 | 1000 |
| 980 | 91/3.70 | 40.7 | 2716 | 0.0302 | 14500 | 142245 | 2380 | 1000 |
| 1030 | 91/3.80 | 41.8 | 2865 | 0.0286 | 15320 | 150289 | 2465 | 1000 |
| 1260 | 91/4.20 | 46.2 | 3501 | 0.0234 | 18350 | 180013 | 2800 | 500 |
| Nominal Cross section area | Structure [number x diameter of wire] | Calculation area cross cestion | Approx. Diameter of conductor | Min.breaking strength | DC Resistance of conductor at 20℃ | Approx Mass of conductor | Current Carrying capacity | |
| mm² | n | mm | mm² | mm | kN | Ω/km | Kg/km | A |
| 120 | 19 | 2.80 | 117.0 | 14.00 | 17.5 | 0.2493 | 320.1 | 566 |
| 150 | 19 | 3.15 | 148.1 | 15.75 | 22.2 | 0.1970 | 405.1 | 659 |
| 200 | 19 | 3.65 | 198.8 | 18.25 | 29.2 | 0.1467 | 543.9 | 798 |
| 240 | 19 | 4.00 | 238.8 | 20.00 | 34.2 | 0.1220 | 654.5 | 897 |
| 300 | 37 | 3.20 | 297.6 | 22.40 | 44.5 | 0.0986 | 816.0 | 1036 |
| 400 | 37 | 3.70 | 397.8 | 25.90 | 58.0 | 0.0737 | 1097.0 | 1258 |
| 510 | 37 | 4.20 | 512.6 | 29.40 | 73.3 | 0.0571 | 1413.0 | 1491 |
| 660 | 61 | 3.70 | 655.9 | 33.30 | 95.6 | 0.0448 | 1812.0 | 1753 |
| 850 | 61 | 4.20 | 845.1 | 37.80 | 120.9 | 0.0342 | 2334.0 | 2073 |
| 980 | 61 | 3.70 | 978.4 | 40.70 | 142.7 | 0.0302 | 2714.0 | 2272 |
| 1030 | 91 | 3.80 | 1032.1 | 41.80 | 150.5 | 0.0286 | 2864.0 | 2353 |
| 1260 | 91 | 4.20 | 1260.8 | 46.20 | 180.3 | 0.0234 | 3499.0 | 2672 |
| 1600 | 127 | 4.00 | 1595.9 | 52.00 | 228.5 | 0.0186 | 4440.0 | 3083 |
| 2020 | 127 | 4.50 | 2019.5 | 58.50 | 289.0 | 0.0147 | 5616.0 | 3540 |
| 2500 | 127 | 5.00 | 2493.7 | 65.00 | 357.0 | 0.0118 | 6937.0 | 3988 |
Scroll horizontally to review complete specification columns.
Request Full TDSTAAAC Conductor Urban network capacity transformation, substation, power plant construction and general lines LEAVE MESSAGE SEND E-MAIL