Technical Grade

ANTI-FRAUD COPPER ALUMINUM- SEU SER

Type SE, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panel board

CategoryService Entrance Cable
SourceDTC Cable

Product Images

Product Overview

Application

SE 型入户电缆主要用于将电力从入户引入线输送至电表底座,再从电表底座输送至配电盘。它也可用于所有允许使用 SE 型电缆的场合。SER 可在干燥或潮湿场所使用,温度不超过 90 °C,额定电压为 600 V。

Standards

• ASTM- All applicable standards • UL Standard 44 for XHHW-2 conductors • UL Standard 83 for THHN/THWN conductors • UL Standard 854 • Federal Specification A-A-59544 • National Electrical Code, NFPA 70. 2011 Edition

Application

SE 型入户电缆主要用于将电力从入户引入线输送至电表底座,再从电表底座输送至配电盘。它也可用于所有允许使用 SE 型电缆的场合。SER 可在干燥或潮湿场所使用,温度不超过 90 °C,额定电压为 600 V。

Standards

• ASTM- B-800 and B-801 • UL Standard 83 for THHN/THWN-2 • UL Standard 44 for XHHW-2 • Federal Specification A-A-59544 • National Electrical Code/NFPA 70, 2011 Edition • RoHS

Technical Parameters

Specification Table 1

Size/ Construction (AWG)StrandingNominal O.D. (mils)Approximate Weight per 1000' (lbs)Allowable Ampacities+Standard Package
Phase & Neutral ConductorsEquipment Ground Conductor60° C75° C90° CDwelling
SER Copper TWO CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS "THREE CONDUCTOR")
8-8-87– –586231405055– –B
6-6-67– –669338556575– –B
MORE
4-4-47– –764498708595100B
3-3-37– –82961185100110110B
2-2-27– –89675295115130125B
1-1-119– –1021948110130150150C
1/0-1/0-1/019– –11141169125150170175C
2/0-2/0-2/019– –12091444145175195200C
3/0-3/0-3/019– –13171792165200225225C
4/0-4/0-4/019– –14382226195230260250C
SER Copper THREE CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS "FOUR CONDUCTOR")
8-8-8-877645286405055– –B
6-6-6-677738424556575– –B
4-4-4-677844585708595100B
3-3-3-57791071985100110110B
2-2-2-47798488795115130125B
1-1-1-319711321117110130150150C
1/0-1/0-1/0-2191912351382125150170175C
2/0-2/0-2/0-1191913421713145175195200C
3/0-3/0-3/0-1/0191914622129165200225225C
4/0-4/0-4/0-2/0191915982650195230260250C
Table values reflect XHHW-2 conductors Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, section 310.15 and 240.4(D). Unless the is marked for use at higher temperaturesthe conductor ampacities shall be limited to the following per NEC 110.14(C) 60 ° C When terminated to equipment for circuits rated 100 amperes or less or marked for 14 – 1 AWG conductors. 75 ° C When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG . 90 ° C XHHW wet or Dry locations for ampacity adjustment purposes using NEC section 310.15 For dwelling ampacity use section 310.15(B)(7)Package Code B- 1000' Reel C- 500' Reel

Specification Table 2

ConductorStrandingNominal O.D. (mils)Approximate Weight per 1000' (lbs)Allowable Ampacities+Standard Package
Size (AWG)Phase ConductorsBare Ground60° C75° C90° CDwelling
SEU Copper ONE CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS "TWO CONDUCTOR")
8-878400144405055– –ABC
6-6712435208556575– –
MORE
4-4712506315708595– –C
2-271558048595115130– –
SEU Copper TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS "THREE CONDUCTOR")
10-10-10112428 X 283127303030– –ABC
8-8-878587 X 380211405060– –ABC
6-6-6712659 X 416308556575– –BCE
4-4-4712815 X 506471708595100BCE
3-3-3712883 X 54858385100110110B
2-2-2715994 X 57871895115130125BD
1-1-119141093 X 664904110130150150B
1/0-1/0-1/019181179 X 7071123125150170175BC
2/0-2/0-2/019181283 X 7671379145175195200BC
3/0-3/0-3/019141429 X 8621712165200225225BD
4/0-4/0-4/019181541 X 9182146195230260250BC
SEU Copper TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS "THREE CONDUCTOR") (REDUCED NEUTRAL)
6-6-878659 X 416281556575– –BC
4-4-6712790 X 481420708595100BC
3-3-5715843 X 50851585100110110BC
2-2-4712929 X 56363995115130125BC
Table values reflect XHHW-2 conductors Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, section 310.15 and 240.4(D). Unless the is marked for use at higher temperaturesthe conductor ampacities shall be limited to the following per NEC 110.14(C) 60 ° C When terminated to equipment for circuits rated 100 amperes or less or marked for 14 – 1 AWG conductors. 75 ° C When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG . 90 ° C XHHW wet or Dry locations for ampacity adjustment purposes using NEC section 310.15 For dwelling ampacity use section 310.15(B)(7)Package Code: A- 250' Coil B- 500' Reel C- 1000' Reel D- 100' Reel E- 150' Coil

Specification Table 3

ConductorStranding*Nominal O.D. (mils)Allowable Ampacities+Approx. Net Weight per 1000' (lbs)Standard Package
Size/Const. AWG or kcmilPhase Conductor & NeutralEquipment Ground Conductor60° C75° C90° CDwelling
SER Aluminum Two Conductor With Bare Ground (Formerly referred to as "EZ-SE")
6-6-67650405060150B
4-4-47745556575203B
MORE
4-4-67745556575203B
2-2-278647590100100290B
2-2-478647590100100290B
2/0-2/0-1121140115135150150527B
2/0-2/0-2/0121140115135150150527B
4/0-4/0-2/0191354150180205200784C
4/0-4/0-4/0191354150180205200784C
SER Aluminum Three Conductor With Bare Ground (Formerly referred to as "Four Conductor")
8-8-8-811612304045136B
6-6-6-677717405060196B
4-4-4-677823556575252B
2-2-2-4779567590100100359B
1-1-1-387107985100115110449C
1/0-1/0-1/0-21011168100120135125540C
2/0-2/0-2/0-11211264115135150150652C
3/0-3/0-3/0-1/01611371130155175175786C
4/0-4/0-4/0-2/01911496150180205200960C
250-250-250-3/022118391702052302251458C
SER Aluminum Four Conductor With Bare Ground (Formerly referred to as "Five Conductor")
2-2-2-2-46710597590100100452B 5
2/0-2/0-2/0-2/0-11211404115135150150827C
4/0-4/0-4/0-4/0-2/019116721501802052001228C
50-250-250-250-3/02211847170205230225C
SEU Aluminum Two Conductor With Bare Concentric Ground (Formerly referred to as "Three Conductor")
6-6-678430 X 687405060145H
4-4-4712499 X 800556575198I
4-4-6715474 X 775556575181I
2-2-2714569 X 9257590100100283I
2-2-4718554 X 9107590100100259I
2/0-2/0-2/01818736 X 1221115135150150514CJ
2/0-2/0-11814720 X 1205115135150150468CJ
4/0-4/0-4/01818878 X 1462150180205205765CL
4/0-4/0-2/01818835 X 1419150180205205691CL
Table values reflect XHHW-2 conductors. +Allowable Ampacities: Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, Section 310.15. 60° C – When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. See NEC Article 338.10(B)(4). 75° C – When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. May not apply, see NEC Article
338.10(B)(4).
90° C – Wet or dry locations. For ampacity derating purposes.
Dwelling – For units, conductors shall be permitted at listed ampacities as 120/240-volt, 3-wire, single-phase services and feeders per NEC Article 310.15.
*For compact-stranded construction, the number of wires, as permitted by UL Standard 83, UL Standard 854, and ASTM B-801, may be reduced as follows:
19-Wire Constructions – 18 Wires Minimum

Scroll horizontally to review complete specification columns.

Request Full TDS

Structure & Technical Illustration

应用

SE 型入户电缆主要用于将电力从入户引入线输送至电表底座,再从电表底座输送至配电盘。它也可用于所有允许使用 SE 型电缆的场合。SER 可在干燥或潮湿场所使用,温度不超过 90 °C,额定电压为 600 V。

Product image and technical reference.

Related Products

单相 concentric aluminium 电缆-Kenya

单相 concentric aluminium 电缆-Kenya

View Details
一次 UD TRXLPE PVC 同心中性线 5-46kv

一次 UD TRXLPE PVC 同心中性线 5-46kv

View Details
同心及分体同心电缆-BS

同心及分体同心电缆-BS

View Details
入户同心电缆-AFRICA

入户同心电缆-AFRICA

View Details
ANTI-FRAUD COPPER ALUMINUM- SEU SER | DTC Cable